Protocole Modbus

I. Introduction

1.1 Scope

MODBUS is an application layer messaging protocol on layer 7 of the OSI model that provides client/server communication between devices connected to different types of buses or networks.

Since its emergence in 1979 as the de facto standard for industrial serial links, MODBUS has enabled thousands of automation devices to communicate. Currently, support for the simple and elegant MODBUS structure continues to be added. Internet organizations enable access to MODBUS via the reserved system port 502 on the TCP/IP stack.

MODBUS is a request/response protocol and provides services specified by function codes. MODBUS function codes are elements of the MODBUS request/response PDU. The purpose of this document is to describe the function codes used within the MODBUS transaction processing framework. 1.2 Normative reference documents 1. RFC791, Internet Protocol, Sep81 DARPA 2. MODBUS Protocol Reference Guide Rev J, MODICON, June 1996, doc#PI_MBUS_300 MODBUS is an application layer messaging protocol used for client/server communications between devices connected through different types of buses or networks. Currently, MODBUS is implemented using: TCP/IP over Ethernet. Asynchronous serial transmission over various media (wired: EIA/TIA-232-E, EIA-422, EIA/TIA-485-A; fiber optic, wireless, etc.). MODBUS PLUS, a high-speed token passing network.

1.2 Normative reference documents

1. RFC791, Internet Protocol, Sep81 DARPA

2. MODBUS Protocol Reference Guide Rev J, MODICON, June 1996, doc#PI_MBUS_300 MODBUS is an application layer messaging protocol used for client/server communications between devices connected through different types of buses or networks.

Currently, MODBUS is implemented using: TCP/IP over Ethernet.

Asynchronous serial transmission over various media (wired: EIA/TIA-232-E, EIA-422, EIA/TIA-485-A; fiber optic, wireless, etc.). MODBUS PLUS, a high-speed token passing network.

2 Abbreviations

ADU Application Data Unit

HDLC Advanced Data Link Control

HMI human machine interface

IETF Internet Engineering Working Group I/O Input/Output Device IP Internet Protocol

MAC media access control

MB MODBUS protocol

MBAP MODBUS protocol

PDU protocol data unit

PLC programmable logic controller

TCP Transmission Control Protocol

3 Background summary

The MODBUS protocol allows simple communication within a variety of network architectures.

Every device (PLC, HMI, control panel, driver, motion control, input/output device) can use the MODBUS protocol to initiate remote operation.

The same communication is possible over MODBUS over serial links and Ethernet TCP/IP networks.

Some gateways allow communication between several buses or networks using the MODBUS protocol.

4 General description

4.1 Protocol description

The MODBUS protocol defines a simple protocol data unit (PDU) that is independent of the underlying communication layer.on a specific bus or network

The MODBUS protocol mapping can introduce some additional fields on the application data unit (ADU).

A client that initiates a MODBUS transaction creates a MODBUS application data unit. Function codes indicate to the server which operation will be performed.

The MODBUS protocol establishes a client-initiated request format.

Use one byte to encode the function code field of the MODBUS data unit. The valid codeword range is decimal 1-255 (128-255 are reserved for exception responses). When a message is sent from the client to the server device, the function code field tells the server what operation to perform.

Add sub-function codes to some function codes to define multiple operations.

The data field of the message sent from the client to the server device includes additional information, and the server uses this information to perform the operation defined by the function code. This field also includes discrete item and register addresses, the number of items processed, and the actual number of data bytes in the field.

In certain requests, the data field can be non-existent (0 length), in which case the server does not require any additional information. Function codes only describe operations.

If no errors related to the requested MODBUS functionality occurred in a correctly received MODBUS ADU, the server-to-client response data field includes the request data. If an error occurs related to requesting MODBUS functionality, the field includes an exception code that the server application can use to determine the next operation to perform.

For example, a client can read the on/off status of a set of discrete outputs or inputs, or a client can read/write the data contents of a set of registers.

When the server responds to the client, it uses the function code field to indicate a normal (error-free) response or something went wrong (called an exception response). For a normal response, the server only responds to the original function code.

DTU/Edge Gateway/Plate-forme IoT/Module de passerelle

For an exception response, the server returns a code equal to the original function code and sets the most significant bit of the original function code to logic 1.

DTU/Edge Gateway/Plate-forme IoT/Module de passerelle

Comment: Timeouts need to be managed to explicitly wait for a reply that may not come.

The length constraint of the first MODBUS implementation on the serial link limits the MODBUS PDU size (maximum RS485ADU=256 bytes).

Therefore, for serial link communication, MODBUS PDU = 256 – server address (1 byte) – CRC (2 bytes) = 253 bytes.

thereby:

RS232 / RS485 ADU = 253 bytes Server address (1 byte) CRC (2 bytes) = 256 bytes.

TCP MODBUS ADU = 249 bytes MBAP (7 bytes) = 256 bytes.

The MODBUS protocol defines three types of PDUs. They are:

MODBUS request PDU, mb_req_pdu

MODBUS response PDU, mb_rsp_pdu

MODBUS exception response PDU, mb_excep_rsp_pdu

Define mb_req_pdu as: mb_req_pdu = { function_code, request_data}, where

function_code – [1 byte] MODBUS function code

request_data – [n bytes], this field is related to the function code and usually includes information such as variable references, variables, data offsets, sub-function codes, etc.

Define mb_rsp_pdu as:

mb_rsp_pdu = { function_code, response_ data}, where

function_code – [1 byte] MODBUS function code

response_data – [n bytes], this field is related to the function code and usually includes information such as variable references, variables, data offsets, sub-function codes, etc.

Define mb_excep_rsp_pdu as:

mb_excep_rsp_pdu = { function_code, request_data}, where

function_code – [1 byte] MODBUS function code 0x80

exception_code – [1 byte], MODBUS exception codes are defined in the table below.

4.2 Data encoding

MODBUS uses a ‘big-Endian’ representation of addresses and data items. This means that when multiple bytes are transmitted, the most significant bit is sent first.For example: register size value

16 – Bit 0x1234 The first byte sent is 0x12 then 0x34

Note: See [1] for more detailed information.

4.3 MODBUS data model

MODBUS is based on a series of data models on tables with different characteristics. The four basic forms are:

basic form Object type access type content
Discrete input single bit read only The I/O system provides this type of data
Coil single bit Read and write Change this type of data through the application
input register 16-bit word read only The I/O system provides this type of data
holding register 16-bit word Read and write Change this type of data through the application

The distinction between input and output and between bit-addressed and word-addressed data items does not imply any application operation. If this is the most natural explanation for the core of the suspect object, then this distinction is perfectly acceptable and commonplace, so that all four tables are considered to cover one another.

For any item in the basic table, the protocol allows 65536 data items to be selected individually, and read and write operations on those items are designed to span multiple consecutive data items up to the data size specification limit, which is consistent with the transaction processing function code related.

Obviously, all data processed via MODBUS must be placed in the device application memory. However, the physical address of the memory should not be confused with the data reference. The requirement is simply that the data reference is linked to a physical address.

The MODBUS logical reference number used in the MODBUS function code is an unsigned integer index starting from 0.

Examples of MODBUS model implementation

The following examples show two ways of structuring data in the device. There may be different structures, not all described in this document. Each device has its own data structure based on its application.

Example 1: Device with 4 independent blocks

The following example shows the data structure in a device that contains digital and analog quantities, inputs and outputs. Since the data in different blocks are not related, each block is independent of each other. Access each block according to different MODBUS function codes.

DTU/Edge Gateway/Plate-forme IoT/Module de passerelle

Example 2: Device with only 1 block

In this example, the device has only 1 data block. It is possible to obtain the same data via several MODBUS function codes, or via 16-bit access or 1 access bit.

DTU/Edge Gateway/Plate-forme IoT/Module de passerelle

4.4 Definition of MODBUS transaction processing

The following state diagram describes the general processing of MODBUS transactions on the server side.

DTU/Edge Gateway/Plate-forme IoT/Module de passerelle

Once the server processes the request, it builds a MODBUS response using the appropriate MODBUS server transaction.

Depending on the processing results, two types of responses can be established:

● A positive MODBUS response:

● Response function code = Request function code

● A MODBUS exception response (see Section 6.14)

● Used to provide the client with information related to errors discovered during processing;

● Response function code = request function code 0x80;

● Provide an exception code to indicate the cause of the error.

5 Function code classification

There are three types of MODBUS function codes. They are:

● Is a well-defined function code,

● Guaranteed to be unique,

● MODBUS organization can be changed,

● Publicly proven,

● Have conformance tests available,

● As demonstrated in the MB IETF RFC,

● Contains defined public assigned function codes and unassigned reserved function codes for future use.

User defined function code

● There are two definition ranges of user-defined function codes, namely 65 to 72 and decimal 100 to 110.

● The user can select and implement a function code without any approval from the MODBUS organization

● There is no guarantee that the selected function code will be used uniquely.

● If the user wants to reset the function as a public function code, the user must initiate an RFC to introduce the change into the public category and assign a new public function code.

Reserve function code

● Function codes that are commonly used by some companies for traditional products and are invalid for public use.

DTU/Edge Gateway/Plate-forme IoT/Module de passerelle

5.1 Definition of public function codes

DTU/Edge Gateway/Plate-forme IoT/Module de passerelle

6 Function code description

6.1 01 (0x01) read coil

In a remote device, use this function code to read the continuous status of the coil from 1 to 2000. The request PDU details the starting address, the first coil address specified, and the coil number. Addressing the coil starts from zero. So addressing coils 1-16 is 0-15.

The coil in the response message is divided into one coil according to each bit of the data field. Indicated status is 1= ON and 0= OFF. The LSB (least significant bit) of the first data byte contains the output addressed in the interrogation. The other coils follow this sequence, up to the high end of this byte, and from low to high in subsequent bytes.

If the number of outputs returned is not a multiple of eight, the remaining bits in the last data byte (up to the high-order end of the byte) will be padded with zeros. The number of bytes field specifies the complete number of bytes of data.

Request PDU

function code 1 byte 0x01
initial address 2 bytes 0x0000 to 0xFFFF
Number of coils 2 bytes 1 to 2000 (0x7D0)

Response PDU

function code 1 byte 0x01
Number of bytes 1 byte N*
coil status N bytes n=N or N 1

*N=Output quantity/8, if the remainder is not equal to 0, then N = N 1

mistake

function code 1 byte Function code +0x80
Exception code 1 byte 01 or 02 or 03 or 04

This is an example of a request to read discrete outputs 20-38:

ask response
domain name (hexadecimal) domain name (hexadecimal)
Fonction 01 Fonction 01
Starting address Hi 00 Number of bytes 03
Starting address Lo 13 Output status 27-20 CD
Output quantityHi 00 Output status 35-28 6B
Output quantity Lo 13 Output status 38-36 05

Represent the status of output 27-20 as the hexadecimal byte value CD, or 1100 1101 in binary. Output 27 is the MSB of this byte and output 20 is the LSB.

Typically, the bits within a byte are represented with the MSB on the left and the LSB on the right. The output of the first byte is 27 to 20 from left to right. The output of the next byte is 35 to 28 from left to right. When bits are transmitted serially, from LSB to MSB: 20 ​​. . . 27, 28 . . . 35, and so on.

In the last data byte, output status 38-36 is represented as a hexadecimal byte value of 05, or 0000 0101 in binary. Output 38 is the sixth bit position from the left, and output 36 is the LSB of this byte. Fill the five remaining high-order bits with zeros.

Note: Fill the five remaining bits (up to the high-order bit) with zeros.